Air conditionning controllers / Chillers and Heat pumps controllers / iCHILL - IC200L - IC200D series

IC281L
Advanced multifunction controllers for chiller with heat pump and chillers with free cooling and with partial or total heat recovery (2 circuits up to 6 compressors)

DIXELL France Logo DIXELL France Logo
IC281L - Air conditionning controllers
L: 38x185mm, panel mounting
© DIXELL France
19-21 Avenue JOFFRE
93800 EPINAY-SUR-SEINE - France
Tel: +33(0)1.41.68.20.00
Fax:
www.dixell.fr/english
 
Features
--
First display   3 digits, d.p., -
--
Second display   4 digits, d.p., -
--
Keyboard   8 push buttons
--
Power supply   12Vac/dc, 24Vac/dc optional
--
Probe inputs
--
All Probes   NTC/PTC/4÷20mA/0÷5V
10 configurable
--
Digital inputs
--
N° Digital inputs   18 configurable
--
Relay outputs
--
N° relay outputs   14 of 5A
--
Other Outputs
--
Hot Key/Prog Tool
Kit output
  present
--
Remote keyboard output   VI820 (up to 2)
--
Serial output   TTL
--
PWM outputs for condensing fan   2
--
0÷10V or 4÷20mA outputs for condensing fan   2 configurable
--
0÷10V outputs for free cooling, heat recovery, external relay   4 configurable
--
Other
--
Buzzer   optional
--
Real time clock   optional
--
Measurement
--
Measurement range   Pressure probe: 0÷50bar
NTC probe: -30÷70°C (-22÷158°F)
PTC probe: 0÷150°C (32÷302°F)
--
Accuracy   ±0.7°C ±1digit
--
Generals
--
Housing   Self extinguishing ABS
--
Front protection   IP 65 with gasket
--
Power absorption   10VA max
--
Display type   1st: red LED (8.0mm high)
2nd: yellow LED (5.6mm high)
--
Data Storage   EEPROM memory
--
Operating temperature   -10°÷60°C
14°÷140°F
--
Storage temperature   -30°÷85°C
-22°÷185°F
--
Relative humidity   20÷85% (non condensing)
--
Resolution   0.1°C or 1°F (selectable)
--
Connection   Disconnectable connectors
(12-14 pin or 14-6 pin or 16-8 pin)
--
click here to enlarge
 
28.03.2024
Non-contractual document. The continuous improvement of Dixell's products can cause some variations in the information included in this catalogue even without notice.