L: 38x185mm, panel mounting |
|
|
|
© DIXELL France
19-21 Avenue JOFFRE
93800 EPINAY-SUR-SEINE - France
Tel: +33(0)1.41.68.20.00
Fax:
www.dixell.fr/english
|
|
|
|
Features |
|
First display |
|
3 digits, d.p., - |
|
Second display |
|
4 digits, d.p., - |
|
Keyboard |
|
6 push buttons |
|
Power supply |
|
12Vac/dc, 24Vac/dc optional 110, 230Vac |
|
|
Probe inputs |
|
Pb1 |
|
NTC - configurable |
|
Pb2 |
|
NTC - configurable |
|
Pb3 |
|
NTC/4÷20mA configurable |
|
Pb4 |
|
NTC/dig inp configurable |
|
|
Digital inputs |
|
Low pressure switch |
|
present |
|
High pressure switch |
|
present |
|
N° Digital inputs |
|
4 configurable |
|
|
Relay outputs |
|
RL1 Compressor 1 |
|
8A |
|
RL2 |
|
8A configurable |
|
RL3 |
|
8A configurable |
|
RL4 |
|
8A configurable |
|
RL5 |
|
8A configurable optional |
|
|
Other Outputs |
|
Hot Key/Prog Tool Kit output |
|
present |
|
Remote keyboard output |
|
present (for VI610) |
|
Serial output |
|
TTL |
|
Alarm output |
|
12Vdc - 40mA max |
|
Analog output |
|
4÷20mA for fan speed module-optional |
|
Signal output for triac or on/off fan module |
|
PWM |
|
|
Other |
|
Buzzer |
|
optional |
|
Real time clock |
|
optional |
|
|
Measurement |
|
Measurement range |
|
Pressure probe: 0÷50bar NTC probe: -40÷110°C (-40÷230°F) |
|
Accuracy |
|
±0.7°C ±1digit |
|
|
Generals |
|
Housing |
|
Self extinguishing ABS |
|
Front protection |
|
IP 65 with gasket |
|
Power absorption |
|
5VA max |
|
Display type |
|
1st: red LED (8.0mm high) 2nd: yellow LED (5.6mm high) |
|
Data Storage |
|
EEPROM memory |
|
Operating temperature |
|
-10°÷60°C 14°÷140°F |
|
Storage temperature |
|
-30°÷85°C -22°÷185°F |
|
Relative humidity |
|
20÷85% (non condensing) |
|
Resolution |
|
0.1°C or 1°F (selectable) |
|
Connection |
|
Disconnectable connectors (12-14 pin or 14-6 pin or 16-8 pin) |
|
|
|
|
18.04.2024 |
Non-contractual document. The continuous improvement of Dixell's products can cause some variations in the information included in this catalogue even without notice. |
|
|
|